Wire Gauge and Voltage Drop Calculator

Sizing by both criteria at once — heating per DIN VDE 0298-4 and voltage drop per HD 60364-5-52 Annex G. Result in mm², AWG and SWG.

Recommended size
mm²
Permissible load
0W
AWG SWG
for the selected size and conditions
Voltage drop0 V · 0%
Voltage at load0 V
Power loss0 W
Heat output0 W/m
Ampacity Iz0 A
Conductor temperature0 °C
Iz = Itable · f1 · f2 · f4
Custom size mm²
Compliance check
Load current Ib 5 A
Run length 3 m
One way — the return conductor is included automatically
Voltage 24 V
Current type
Material
Power factor cos φ 1.00
Reactance of 0.08 mΩ/m is included per HD 60364-5-52 Annex G
Not applicable to direct current
Installation method
Reference methods A2 / B2 / C / E per DIN VDE 0298-4, Table 2
Ambient temperature 30 °C
Grouping f2 = 1.00
Circuits alongside 1
Tables 22 and 28 of DIN VDE 0298-4. A neutral of a balanced circuit is not counted, PE never is.
Design margin +25%
Not a requirement of the standard but a designer's margin. Applied to size selection only.
Permissible drop 3%
3% per DIN 18015-1 for dwellings, 5% for other circuits per Annex G
Short-circuit withstand k = 115
Fault current, kA
Disconnection time, s
Adiabatic minimum0 mm²
Limit time0 s
S ≥ √(I²t)/k per IEC 60364-4-43, Table 43.1
Neutral conductor N 3-phase
mm²
AWG
Neutral current0 A
Factor f41.00
Third harmonic content
Appears when three-phase supply is selected
Wire size converter: mm² ↔ AWG ↔ SWG
converter

Enter a value in any field — the other two are recalculated automatically.

mm²
Metric cross-section
AWG
American Wire Gauge
SWG
British Standard Wire Gauge
Conductor diameter0 mm
Nearest standard size mm²
Iz, clipped to a wall (C) A
Iz, in conduit or trunking (B2) A
Copper resistance at 20 °C0 mΩ/m

Iz is given for copper with PVC insulation, two loaded conductors, 30 °C, no grouping. A dash means the size falls outside the table of the standard — no extrapolation is done here.

Reference calculation. The size is chosen by the greater of two criteria: permissible heating per DIN VDE 0298-4:2023-06 (Tables 2 and 11 with factors from Tables 17, 22, 28 and B.1) and permissible voltage drop per HD 60364-5-52 Annex G. Heat output is given per metre of the run. Fixed wiring is subject to local regulations, and the protective device is rated to the cable, not to the load.

Powered by SpecLED Cable Cross-Section Calculator by Current and Power: Voltage Drop Calculation, SWG to AWG to mm² Converter